Author: Cho, Wan-Ho; Jeong, Cheol-Ho; Chang, Ji-Ho; Lee, Seong-Hyun; Park, Moo Kyun; Suh, Myung-Whan; Han, Jae Joon
Title: Noise and Room Acoustic Conditions in a Tertiary Referral Hospital, Seoul National University Hospital
  • Document date: 2019_4_10
  • ID: tqos2539_23
    Snippet: The noise levels measured in ERs, 52 to 56 dBA, were quite lower than in most previous studies. LAeq in the emergency department of Johns Hopkins hospital ranges from 65 to 73 dBA [6] , which is at least 10 dB higher than in SNUH. This is possibly due to the cultural aspect and new refurbishment. The entire emergency department at SNUH was refurbished throughout 2017, to have a triage area in the middle, being connected to several small treatment.....
    Document: The noise levels measured in ERs, 52 to 56 dBA, were quite lower than in most previous studies. LAeq in the emergency department of Johns Hopkins hospital ranges from 65 to 73 dBA [6] , which is at least 10 dB higher than in SNUH. This is possibly due to the cultural aspect and new refurbishment. The entire emergency department at SNUH was refurbished throughout 2017, to have a triage area in the middle, being connected to several small treatment rooms with a small number of beds as shown in Fig. 1A . The main reason for the refurbishment was to prevent the spread of contagious disease, such as Middle East respiratory syndrome. The medical staff mentioned that overall noise level in ERs has been reduced after the refurbishment. Recent measurements in Danish hospitals for 4-5 days shows 56 to 58 dBA [30] , and these values are as low as the measured value in the present study.